| LPHW THERMAL OUTPUT - WATTS/METRE | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Mean Water Temperature | ||||||||||||
| 40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
85 |
90 | ||
| TRENCH 180 |
121 |
166 |
211 |
262 |
313 |
369 |
425 |
486 |
546 |
611 |
675 | |
| TRENCH 250 |
179 |
247 |
315 |
393 |
470 |
556 |
641 |
733 |
825 |
924 |
1023 | |
| ENTERING AIR TEMPERATURE 20°C (NORMAL ROOM TEMPERATURE) | ||||||||||||
| WATER VELOCITY CORRECTION FACTOR | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| The thermal output figures are based on a velocity of 1.0Metre/Sec. For other velocities the following factors should be applied. | |||||||||||
| VELOCITY (M/SEC) |
0.05 |
0.10 |
0.20 |
0.30 |
0.40 |
0.50 |
0.60 |
0.80 |
1.00 |
1.50 |
2.00 |
| CORRECTION FACTOR |
0.86 |
0.91 |
0.91 |
0.95 |
0.96 |
0.97 |
0.98 |
0.99 |
1.00 |
1.02 |
1.03 |
| AMBIENT TEMPERATURE CORRECTION |
|
The thermal output figures are based on an ambient temperature of 20OC and may be corrected for other ambient temperatures in the range of 0OC to 40OC by multiplying by the factor “R”.
TESTED TO BS EN 442-2: 1997 where R = T-Ta T = Mean temperature of heating medium °C. T-20 Ta = Ambient Temperature °C. |
TESTED TO BS EN 442-2: 1997